Electrical Insulating Matting (Switchboard Matting)

Electrical Insulating Matting (Switchboard Matting)

Boddingtons Electrical Ltd manufacture a range of electrical insulating matting , often referred to as switchboard matting

Rubber is known for its exceptional electrical insulating properties. With the ability to reduce or stop electric currents, electrical rubber matting or switchboard matting is a common surface for high voltage environments. Used to protect workers from electrical shocks it is ideal for plant rooms, control rooms, switchboards and places where individuals handle live equipment.

We offer the most extensive and compliant range of Electrical Safety Matting/Switchboard Matting in the UK - IEC61111 (all classes), ASTM D178, BS 921

The European standard IEC 61111:2009 that has replaced the national standards of the EU countries assorts the electrical insulating matting as per its resistance to high tension breakdown into 5 classes.

  • Class 0 - Working voltage: 1 000 V - Proof voltage: 5 000 V -  Withstand voltage: 10 000 V
  • Class 1 - Working voltage: 7 500 V - Proof voltage: 10 000 V - Withstand voltage: 20 000 V
  • Class 2  - Working voltage: 17 000 V - Proof voltage: 20 000 V - Withstand voltage: 30 000 V
  • Class 3 - Working voltage: 26 500 V - Proof voltage: 30 000 V - Withstand voltage: 40 000 V
  • Class 4 - Working voltage: 36 000 V - Proof voltage: 40 000 V - Withstand voltage: 50 000 V